Last Updated: 05.28.2026 15:42:50Filters: 05/26/2026 to 05/28/2026; Include PJM Drill
Emergency Message
105190
Post Contingency Local Load Relief Warning
Warning
05.28.2026 09:13
DOM
A Post Contingency Local Load Relief Warning has been issued to maintain BECO-PACIFIC 2165A at 1093.0 MVA in the DOM for Transmission Contingency Control. Additional Comments: Load -No Generation or Switching available
105189
Post Contingency Local Load Relief Warning
Warning
05.27.2026 20:50
05.27.2026 21:43
FE-AP
A Post Contingency Local Load Relief Warning has been issued to maintain RINGGOLD T4 XFORMER at 214.0 MVA in the FE(APS) for Transmission Contingency Control. Additional Comments: Load -No Generation or Switching available
105188
Post Contingency Local Load Relief Warning
Warning
05.27.2026 19:03
05.27.2026 23:43
DOM
A Post Contingency Local Load Relief Warning has been issued to maintain LOUDOUN4 569T584 CB at 3264.0 MVA in the DOM for Transmission Contingency Control. Additional Comments: Load -No Generation or Switching available
105187
Post Contingency Local Load Relief Warning
Warning
05.27.2026 17:59
05.27.2026 23:45
DOM
A Post Contingency Local Load Relief Warning has been issued to maintain PLYWOOD-SEDGEHIL 151A at 162.0 MVA in the DOM for Transmission Contingency Control. Additional Comments: Load -No Generation or Switching available
Drill
105186
DRILL - Manual Load Dump ActionPotential PAI
Action
05.27.2026 12:30
05.27.2026 13:45
PJM-RTO
A Manual Load Dump Action of 2000 MW and an EEA3 have been requested. Total load shed from all active Manual Load Dump Actions within this Region is 2000 MW. Additional Comments: This is a drill only. . MIDATL share 865 MW . AEP share 195 MW . FE South (AP) share 145 MW . DAYT share 57 MW . DLCO share 58 MW . CE share 125 MW . DOM share 266 MW . FE West share 180 MW . CPP share 5 MW . DEOK share 90 MW . EKPC share 14 MW
Drill
105185
DRILL - Curtailment of Non-Essential Building LoadPotential PAI
Action
05.27.2026 12:00
05.27.2026 14:30
PJM-RTO
A Curtailment of Non-Essential Building Load Action has been issued to provided additional load relief reductions. Transmission/Generation dispatchers/LSEs switch off all non-essential light and power in LSE-owned commercial, operations, and administration offices. Additional Comments: This is a drill only.
Drill
105184
DRILL - Voltage Reduction ActionPotential PAI
Action
05.27.2026 12:00
05.27.2026 14:30
PJM-RTO
A Voltage Reduction Action of 5 % and a NERC level EEA2 have been issued for PJM RTO . NOTE: Curtailment of Non-Essential Building Load should be issued prior to, but no later than the same time as a Voltage Reduction. Additional Comments: This is a drill only.
Drill
105183
DRILL - Maximum Generation Emergency ActionPotential PAI
Action
05.27.2026 11:45
05.27.2026 14:30
PJM-RTO
A Maximum Generation Emergency Action has been issued. Additional Comments: This is a drill only. PJM is requesting all FUEL LIMITED GENERATION be loaded and all REGULATION (EXCEPT HYDRO UNITS) SUSPENDED.
Drill
105181
DRILL - Manual Load Dump WarningPotential PAI
Warning
05.27.2026 11:25
05.27.2026 14:30
PJM-RTO
A Manual Load Dump Warning has been issued as of 11:25 on 05.27.2026 Additional Comments: This is a drill only. . MIDATL share 865 MW . AEP share 195 MW . FE South (AP) share 145 MW . DAYT share 57 MW . DLCO share 58 MW . CE share 125 MW . DOM share 266 MW . FE West share 180 MW . CPP share 5 MW . DEOK share 90 MW . EKPC share 14 MW
Drill
105180
DRILL - Deploy All Resources ActionPotential PAI
Action
05.27.2026 11:15
05.27.2026 14:30
PJM-RTO
A Deploy All Resources Action , and associated NERC Energy Emergency Alert Level 2 [EEA2], has been issued. - Member Generation Dispatchers raise all available online generating units to full output (Emergency Maximum). - Member Generation Dispatchers start up all offline generation as soon as possible and ramp to full output (Emergency Maximum). - Member Curtailment Service Providers with Load Management (Pre-Emergency and/or Emergency) reduce load immediately when dispatched. - Transmission/Generation Dispatchers notify management of the emergency procedure and that they should consider the use of public appeals to conserve electricity usage. - Member dispatchers notify governmental agencies, as applicable. Additional Comments: This is a drill only.
Drill
105182
DRILL - Maximum Generation Emergency ActionPotential PAI
Action
05.27.2026 11:00
05.27.2026 14:30
PJM-RTO
A Maximum Generation Emergency Action has been issued. Additional Comments: This is a drill only. PJM is requesting that all MAXIMUM EMERGENCY Steam be loaded.
Drill
105179
DRILL - Voltage Reduction Warning and Reduction of NCPLPotential PAI
Warning
05.27.2026 10:45
05.27.2026 14:30
PJM-RTO
A Voltage Reduction Warning and Reduction of NCPL has been issued. Actual Synchronized (or Spinning) Reserves are less than the Synchronized (or Spinning) Reserve requirement. PJM Member Actions: 1. Generation dispatchers order all generating stations to curtail non-essential station light and power. Additional Comments: This is a drill only
Drill
105178
DRILL - Emergency Voluntary Energy Only Demand Response
Action
05.27.2026 10:30
05.27.2026 14:30
PJM-RTO
An Emergency Voluntary Energy Only Demand Response Reduction Action has been issued. Load reduction is expected to be implemented as soon as possible and is requested to remain reduced as long as possible or until cancelled by PJM. CSPs should review DR Hub for specific registration details. Dispatched Control Zone(s) only. Additional Comments: This is a drill only
Drill
105177
DRILL - Maximum Generation Emergency ActionPotential PAI
Action
05.27.2026 10:15
05.27.2026 14:30
PJM-RTO
A Maximum Generation Emergency Action has been issued. Additional Comments: This is a drill only. PJM requesting the loading of Maximum Emergency Generation for CT units Only.
Drill
105176
DRILL - Primary Reserve Warning
Warning
05.27.2026 10:00
05.27.2026 14:30
PJM-RTO
A Primary Reserve Warning has been issued from 10:00 on 05.27.2026 through 14:30 on 05.27.2026 Actual primary reserves are lesser than the requirement. Primary Reserve Objective is 2595 MW. Additional Comments: This is a drill only.